Uninterruptible Power Supplies

UPS 6-10 kVA – Deltron 106 Series

High-Efficiency Power Protection

Power range
6 – 10 kVA
Phase
Single phase (1/1)
Series
Deltron 106 Series
Category
Uninterruptible Power Supplies
Deltron 6-10 kVA tower online UPS

Overview

High-Efficiency Power Protection

Provides double-conversion online protection with zero transfer time, wide input range, and advanced communication interfaces for critical applications.

Features

Characteristics

  • High frequency on-line double conversion technology
  • Advanced DSP and 3-level technology
  • Output power factor 1.0
  • Active power factor correction (APFC), input power factor up to 0.99
  • High efficiency 95% (up to 98% in ECO mode)
  • Advanced digital parallel technology
  • Wide input voltage range (110 ~ 288 Vac) and frequency range (40 ~ 70 Hz)
  • 50 / 60 Hz frequency auto sensing
  • Two modes of frequency conversion: 50 Hz input / 60 Hz output or 60 Hz input / 50 Hz output
  • Dual-input design, supporting independent bypass
  • Flexible battery configuration (settable 16 – 20 pcs batteries)
  • Digitally controlled charger
  • High charging current available (Max. 12 A)
  • Charging voltage and current configured by demands
  • Linear derating in low voltage input reducing battery discharging times, extending the service life of battery
  • Intelligent battery management, automatic floating / equalizing charge control, charger dormancy control, increasing battery life by 50%
  • Ability to switch on the UPS with batteries
  • Settable delayed start time when mains power is restored, reducing the impact on power grid or generator
  • Fan speed varies intelligently with temperature, reducing noise and extending its service life
  • Equipped with self-aging function
  • Compact internal layout, miniaturized the complete unit for small footprint
  • LCD+LED display, multi-functional keys operation, friendly human-machine interface
  • Powerful background software for parameters configuration
  • Advanced multi-platform communications: RS232, USB, RS485, SNMP and dry contacts communication interfaces
  • Effective software and hardware protection function, robust self-diagnostic function, and abundant event log for check

Available Options

  • RS232 and smart card slot included
  • Optional parallel function, battery temperature compensation, SNMP card, USB, RS485 card, dry contacts, EMD, and SMS alarms

Technical specifications

UPS 6-10 kVA – Deltron 106 Series – technical data

Technical specifications – Deltron 106 / 110
Model Deltron 106Deltron 110
Capacity 6 kVA / 6000 W10 kVA / 10000 W
Input
Input wiring Single-phase three-wire (1Φ + N + PE)
Rated voltage 208 / 220 / 230 / 240 Vac
Voltage range 110 – 176 Vac (linear derating between 50% and 100% load); 176 – 288 Vac (no derating)
Rated frequency 50 / 60 Hz (auto-sensing)
Frequency range 40 – 70 Hz
Power factor ≥ 0.99
Bypass voltage range −40% – +15% (settable)
Total harmonic distortion (THDi) ≤ 5%
Output
Output wiring Single-phase three-wire (1Φ + N + PE)
Rated voltage 208 (PF = 0.9) / 220 / 230 / 240 Vac
Voltage regulation ±1%
Frequency Synchronized to bypass in mains mode; 50 / 60 Hz ±0.1 Hz in battery mode
Waveform Sinusoidal
Power factor 1
Total harmonic distortion (THDv) ≤ 1% (linear load); ≤ 4% (non-linear load)
Crest factor 3:1
Overload 105 – 110% for 10 min, 110 – 125% for 1 min, 126 – 150% for 30 s
Batteries
DC voltage 192 Vdc (192 – 240 Vdc settable)
Number of battery 16 pcs (16 – 20 settable)
Inbuilt battery (standard model) 12 V / 7 Ah × 1612 V / 9 Ah × 16
Charging current Standard model: 1 A; long time model: 5 A (default), 1 – 5 A settable; 12 A (optional)
Recharge time Standard model: 90% capacity restored in 8 hours; long time model: depends on the capacity of battery
System
Efficiency ≥ 94% at 100% load, max. 95% at 60% load, ≥ 98% in ECO mode
Transfer time 0 ms
Protections Short-circuit, overload, overtemperature, battery low voltage, overvoltage, undervoltage and fan failure
Max. number of parallel connections 4
Communications RS232 (standard), USB / RS485 / dry contacts / SNMP / battery temperature compensation (optional)
Display LCD + LED
Others
Operating temperature 0 °C – 40 °C
Storage temperature −25 °C – 55 °C (without battery)
Relative humidity 0 – 95% (non-condensing)
Altitude ≤ 1000 m, derating 1% for each additional 100 m
IP rating IP 20
Noise level at 1 m ≤ 55 dB≤ 58 dB
Dimensions W × D × H (mm) 191 × 465 × 711 (S), 191 × 465 × 350 (H)191 × 495 × 711 (S), 191 × 495 × 350 (H)
Packaged dimensions W × D × H (mm) 310 × 654 × 941 (S), 318 × 595 × 475 (H)310 × 685 × 941 (S), 318 × 617 × 475 (H)
Net weight (kg) 53 (S), 14.5 (H)62 (S), 16.5 (H)
Gross weight (kg) 61 (S), 16 (H)70 (S), 18 (H)

S = standard model with internal batteries, H = long time model for external batteries.

Downloads

Datasheets & manuals

Official Deltron documents for UPS 6-10 kVA – Deltron 106 Series. All files are PDF.

Contact us

Need a UPS sized for your project?

Need support or want to discuss your power protection needs? Our engineers will size the right UPS, stabilizer or transfer switch for your application.