Overview
UPS 10 – 30 kVA – DS Power H Online UPS
The new DS Power range UPS uses the latest DSP technology to be programmed to suit a wide variety of electrical environments without impending its performance. With the DS Power range, efficiency, reliability and functionality are enhanced to levels unattainable with the old analogue technology. This technology does not only create significant increase in MTBF, but the capability of DSP to accurately manipulate signals at very high speed permits all the UPS subsystems to be controlled with greatly increased precision.
3 Level Technology
IGBT rectifier with DSP control. With the 3-Level topology, efficiency, reliability and functionality have been raised to levels unattainable with legacy analog technology.
IGBT Rectifier – DSP Control
DS Power H Online UPS uses the latest DSP technology to be programmed to suit a wide variety of electrical environments without impending its performance. This technology not only creates a significant increase in MTBF, but the DSP’s ability to accurately process signals at very high speed allows all UPS subsystems to be controlled with greatly increased precision.
Features
General Specifications
- True double-conversion
- Output power factor 0.9
- Wide input voltage range
- 50Hz frequency converter mode
- Emergency power off function (EPO)
- Generator compatible
- SNMP+USB+RS-232 multiple communications
- 3-stage extendable charging design for optimized battery performance
- Optional maintenance bypass switch
- Transformerless UPS topology
- Low input current total harmonic distortion (THD)
- High input power factor
- High efficiency up to 93%
- Cold start function
- Static and maintenance by-pass switch
- Output short circuit and overload protection
- External REPO switch input
- 512 events memory (512 events 45000 alarms)
- Clock and calendar (battery supported)
- Automatic battery test, remaining battery time indicator
- Temperature compensated charge system (optional)
- 2 RS232 serial ports and 12 dry contact outputs
- 3 DSP controlled modular structure
- Optional SNMP and MODBUS adaptors
- Optional graphical panel
- Manufactured according to EC Directive; EN62040
- 10 years spare parts support
- 2 years warranty
Technical specifications
UPS 10 – 30 kVA – DS Power H Online UPS – technical data
| Model | 10 kVA | 15 kVA | 20 kVA | 30 kVA |
|---|---|---|---|---|
| Input | ||||
| Voltage | 380/400 VAC 3P + N + G ±20% (415 VAC +15%, −25% optional) | |||
| Frequency | 50 Hz / 60 Hz, ±5% | |||
| Power factor (at 100% load) | > 0.98 | |||
| THDI (*) | < 10 – 12% | |||
| By-pass voltage | 220/230 VAC 1 phase + N, ±10% | |||
| Voltage distortion | 10% | |||
| Protection | Fuses, voltage & frequency tolerance, input power limit, phase sequence indicator | |||
| Output | ||||
| Power (kW) | 9 | 13.5 | 18 | 27 |
| Power factor | 0.9 | |||
| Voltage | 220/230 VAC 3P + N, ±1% (240 VAC optional) | |||
| Frequency | 50 Hz / 60 Hz (adjustable) | |||
| Frequency tolerance | Line synchronized: ±2% / free running: ±0.1% | |||
| Efficiency | up to 93% | |||
| Crest factor | 3:1 | |||
| Overload protection | 100 – 125% load: 10 min, 125 – 150% load: 1 min, > 150% load: by-pass | |||
| Other protections | Advanced short circuit, voltage tolerance, DC balance, regenerative load, current limiting | |||
| Voltage THD | < 3% (at 100% linear load) | |||
| Batteries | ||||
| Type | VRLA AGM / GEL / NiCd | |||
| Battery number | 2 × 30 (±30): 60 | |||
| Float charging voltage | 2 × 405 VDC | |||
| End of discharge voltage | 2 × 300 VDC | |||
| Battery cabinet | Internal | |||
| Battery ambient temperature | 25 °C | |||
| Protections | 3 level alarms, battery fuses, charging current limit, temperature compensation (optional) | |||
| Automatic testing | Standard every 72 hours (adjustable) | |||
| General | ||||
| Standards | EN62040-1, EN62040-2 | |||
| User interface | 4 lines LCD panel, mimic LEDs, 5 vector buttons, buzzer, optional TFT panel | |||
| Indicators | P-N voltage, P-P voltage, current, power, crest factor, frequency, PF, service time | |||
| Advanced | Self diagnostics, 3 maintenance time indicators, calibration over RS232, operating hour meter | |||
| Communication | 2 × RS232 serial ports, 4 standard and 8 optional dry contact alarm relays | |||
| Inputs | EPO input, interactive battery panel input, genset input | |||
| Genset kit | Standard (programmable) | |||
| Software | Standard T-Mon UPS Management Software (3 clients + 1 server management) | |||
| Alarm logging | Standard: with time & date 512 events | |||
| Protections | Power module over-temperature, over current, temperature high alarm | |||
| Temperature range | 0 °C – 40 °C | |||
| Protection degree | IP20 | |||
| Relative humidity | 90% max. (non-condensing) | |||
| Altitude | < 1000 m above sea level | |||
| Acoustic noise | < 57 dBA | < 57 dBA | < 62 dBA | < 62 dBA |
| Weight without batteries (kg) | 87 | 87 | 91 | 100 |
| Dimensions H × W × D (mm) | 1040 × 400 × 815 | |||
| Options | ||||
| Different input / output voltage | Please ask | |||
| Transformer | Galvanic isolation transformer at the input & output | |||
| Software | T-Mon Admin multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients | |||
| Adaptors | SNMP, RS485, remote monitoring panel, MODBUS (RS485 or TCP/IP), USB alarm logger, TCP/IP, GSM/GPRS modem, com port multiplexer | |||
| Parallel operation | up to 8 | |||
(*) Depending on power and input/output conditions.
Downloads
Datasheets & manuals
Official Deltron documents for UPS 10 – 30 kVA – DS Power H Online UPS. All files are PDF.
Related products
More UPS models
1-3kVA
Deltron 101 Series
High-Efficiency Power Protection
View details
6-10kVA
Deltron 106 Series
High-Efficiency Power Protection
View details
10-80kVA
DLT 300 Series
10-80kVA Online UPS are microprocessor controlled, full sine output uninterruptible power supplies produced with PWM (Pulse width modulation) and IGBT technologies. It provides uninterrupted energy for local networks, communication systems, sensitive medical devices, smart engineering measuring devices and industrial automation systems by guaranteeing safe operation thanks to its built-in inverter isolation transformer.
View details