Uninterruptible Power Supplies

UPS 10 – 30 kVA – DS Power H Online UPS

Power range
10 – 30 kVA
Phase
Three phase in / single phase out (3/1)
Series
DS Power H
Category
Uninterruptible Power Supplies
Deltron DS Power three-phase online UPS cabinet

Overview

UPS 10 – 30 kVA – DS Power H Online UPS

The new DS Power range UPS uses the latest DSP technology to be programmed to suit a wide variety of electrical environments without impending its performance. With the DS Power range, efficiency, reliability and functionality are enhanced to levels unattainable with the old analogue technology. This technology does not only create significant increase in MTBF, but the capability of DSP to accurately manipulate signals at very high speed permits all the UPS subsystems to be controlled with greatly increased precision.

3 Level Technology

IGBT rectifier with DSP control. With the 3-Level topology, efficiency, reliability and functionality have been raised to levels unattainable with legacy analog technology.

IGBT Rectifier – DSP Control

DS Power H Online UPS uses the latest DSP technology to be programmed to suit a wide variety of electrical environments without impending its performance. This technology not only creates a significant increase in MTBF, but the DSP’s ability to accurately process signals at very high speed allows all UPS subsystems to be controlled with greatly increased precision.

Features

General Specifications

  • True double-conversion
  • Output power factor 0.9
  • Wide input voltage range
  • 50Hz frequency converter mode
  • Emergency power off function (EPO)
  • Generator compatible
  • SNMP+USB+RS-232 multiple communications
  • 3-stage extendable charging design for optimized battery performance
  • Optional maintenance bypass switch
  • Transformerless UPS topology
  • Low input current total harmonic distortion (THD)
  • High input power factor
  • High efficiency up to 93%
  • Cold start function
  • Static and maintenance by-pass switch
  • Output short circuit and overload protection
  • External REPO switch input
  • 512 events memory (512 events 45000 alarms)
  • Clock and calendar (battery supported)
  • Automatic battery test, remaining battery time indicator
  • Temperature compensated charge system (optional)
  • 2 RS232 serial ports and 12 dry contact outputs
  • 3 DSP controlled modular structure
  • Optional SNMP and MODBUS adaptors
  • Optional graphical panel
  • Manufactured according to EC Directive; EN62040
  • 10 years spare parts support
  • 2 years warranty

Technical specifications

UPS 10 – 30 kVA – DS Power H Online UPS – technical data

Technical specifications – DS Power H 10 – 30 kVA (3/1 phase)
Model 10 kVA15 kVA20 kVA30 kVA
Input
Voltage 380/400 VAC 3P + N + G ±20% (415 VAC +15%, −25% optional)
Frequency 50 Hz / 60 Hz, ±5%
Power factor (at 100% load) > 0.98
THDI (*) < 10 – 12%
By-pass voltage 220/230 VAC 1 phase + N, ±10%
Voltage distortion 10%
Protection Fuses, voltage & frequency tolerance, input power limit, phase sequence indicator
Output
Power (kW) 913.51827
Power factor 0.9
Voltage 220/230 VAC 3P + N, ±1% (240 VAC optional)
Frequency 50 Hz / 60 Hz (adjustable)
Frequency tolerance Line synchronized: ±2% / free running: ±0.1%
Efficiency up to 93%
Crest factor 3:1
Overload protection 100 – 125% load: 10 min, 125 – 150% load: 1 min, > 150% load: by-pass
Other protections Advanced short circuit, voltage tolerance, DC balance, regenerative load, current limiting
Voltage THD < 3% (at 100% linear load)
Batteries
Type VRLA AGM / GEL / NiCd
Battery number 2 × 30 (±30): 60
Float charging voltage 2 × 405 VDC
End of discharge voltage 2 × 300 VDC
Battery cabinet Internal
Battery ambient temperature 25 °C
Protections 3 level alarms, battery fuses, charging current limit, temperature compensation (optional)
Automatic testing Standard every 72 hours (adjustable)
General
Standards EN62040-1, EN62040-2
User interface 4 lines LCD panel, mimic LEDs, 5 vector buttons, buzzer, optional TFT panel
Indicators P-N voltage, P-P voltage, current, power, crest factor, frequency, PF, service time
Advanced Self diagnostics, 3 maintenance time indicators, calibration over RS232, operating hour meter
Communication 2 × RS232 serial ports, 4 standard and 8 optional dry contact alarm relays
Inputs EPO input, interactive battery panel input, genset input
Genset kit Standard (programmable)
Software Standard T-Mon UPS Management Software (3 clients + 1 server management)
Alarm logging Standard: with time & date 512 events
Protections Power module over-temperature, over current, temperature high alarm
Temperature range 0 °C – 40 °C
Protection degree IP20
Relative humidity 90% max. (non-condensing)
Altitude < 1000 m above sea level
Acoustic noise < 57 dBA< 57 dBA< 62 dBA< 62 dBA
Weight without batteries (kg) 878791100
Dimensions H × W × D (mm) 1040 × 400 × 815
Options
Different input / output voltage Please ask
Transformer Galvanic isolation transformer at the input & output
Software T-Mon Admin multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients
Adaptors SNMP, RS485, remote monitoring panel, MODBUS (RS485 or TCP/IP), USB alarm logger, TCP/IP, GSM/GPRS modem, com port multiplexer
Parallel operation up to 8

(*) Depending on power and input/output conditions.