Uninterruptible Power Supplies

UPS 1-3 kVA – Deltron 101 Series

High-Efficiency Power Protection

Power range
1 – 3 kVA
Phase
Single phase (1/1)
Series
Deltron 101 Series
Category
Uninterruptible Power Supplies
Deltron 1-3 kVA tower online UPS with LCD display

Overview

High-Efficiency Power Protection

Provides double-conversion online protection with zero transfer time, wide input range, and advanced communication interfaces for critical applications.

Features

Characteristics

  • High frequency on-line double conversion technology
  • DSP (Digital signal processing) control technology
  • Active power factor correction (APFC), input power factor up to 0.99
  • Output power factor 1.0
  • Wide input voltage range (110V ~ 300Vac)
  • Auto sensing frequency
  • 50 / 60 Hz frequency conversion
  • Digitally controlled charger, charging voltage and current configured by demands
  • High charging current available (Max. 12 A)
  • Cold start
  • Rear ventilation design and variable speed fan
  • Effective software and hardware protection
  • Quick and stable charging, 90% capacity restored in 3h (standard model UPS)
  • Linear derating in low voltage input reducing battery discharging times
  • Advanced battery management (ABM)
  • Multiple functions settable via LCD: output voltage, EOD, auto-start, bypass mode, ECO mode
  • Multi-platform communications: RS232 (standard), USB / RS485 / SNMP / dry contacts (optional)
  • Optional USB, RS485 card, AS400 dry contacts, SNMP card, SMS alarms, EPO function

Technical specifications

UPS 1-3 kVA – Deltron 101 Series – technical data

Technical specifications – Deltron 101 / 102 / 103
Model Deltron 101Deltron 102Deltron 103
Capacity 1 kVA / 1 kW2 kVA / 2 kW3 kVA / 3 kW
Input
Rated voltage 208 / 220 / 230 / 240 Vac
Voltage range 110 – 176 Vac (linear derating between 50% and 100% load); 176 – 280 Vac (no derating); 280 – 300 Vac (derating 50%)
Frequency range 50/60 Hz ±5 Hz (auto-sensing)
Power factor ≥ 0.95≥ 0.99≥ 0.99
Bypass voltage range −40% – +20% (settable)
Rated input frequency 50 Hz / 60 Hz (auto-sense)
THDi ≤ 5%
Output
Voltage 208 / 220 / 230 / 240 Vac (settable via LCD)
Voltage regulation ±1%
Frequency 45 – 55 Hz or 55 – 65 Hz (synchronized range); 50/60 Hz ±0.1 Hz (battery mode)
Waveform Sinusoidal
Power factor 1.0
THDv ≤ 2% (linear load), ≤ 5% (non-linear load)
Crest factor 3:1
Overload 105 – 110% for 30 min, 110 – 130% for 10 min, 130 – 150% for 30 s, > 150% for 500 ms
Batteries
Battery type Sealed lead acid maintenance free battery
DC voltage 24 V (S) / 24 V (H), 36 V (S) / 36 V (H)48 V (S) / 48 V (H), 72 V (S) / 72 V (H)72 V (S) / 72 V (H), 96 V (S) / 96 V (H)
Inbuilt battery (S models) 2 × 9 Ah (24 V), 3 × 7 Ah (36 V)4 × 9 Ah (48 V), 6 × 7 Ah (72 V)6 × 9 Ah (72 V), 8 × 7 Ah (96 V)
Inbuilt battery (H models) – (external battery)
Charging current (max.) 12 A (1 – 12 A settable)
Recharge time Standard model: 90% capacity restored in 3 hours
System control and communications
Efficiency (mains mode) ≥ 93.5%≥ 94.5%≥ 94.5% (S) / ≥ 95.5% (H)
Efficiency (battery mode) ≥ 89% (S) / ≥ 90% (H)≥ 91% (S) / ≥ 92.5% (H)≥ 92.5% (S) / ≥ 93% (H)
Efficiency (ECO mode) ≥ 98.5%≥ 99%≥ 99%
Transfer time Mains mode to battery mode: 0 ms; inverter mode to bypass mode: 4 ms (typical)
Protections Short-circuit, overload, overtemperature, battery discharge protection and fan testing protection
Communication port RS232 (standard), USB / RS485 / SNMP / dry contacts (optional)
Display LCD + LED
Environment
Operating humidity 0 – 95% RH @ 0 – 40 °C (non-condensing)
Storage temperature −25 °C – 55 °C (exclude batteries)
Operating altitude ≤ 1000 m; above 1000 m derating 1% for each additional 100 m
IP rating IP 20
Noise level at 1 m ≤ 50 dB
Others
Dimensions W × D × H (mm) 144 × 312 × 216 (S/H), 144 × 371 × 216 (36 V S)144 × 417 × 216 (S/H), 191 × 419 × 335 (72 V S)191 × 419 × 335 (S), 144 × 417 × 216 (H)
Packaged dimensions W × D × H (mm) 230 × 402 × 315, 230 × 460 × 315 (36 V S)230 × 506 × 315, 277 × 500 × 435 (72 V S)277 × 500 × 435 (S), 230 × 506 × 315 (H)
Net weight (kg) 8.8 / 4.0 (24 V), 10.9 / 4.0 (36 V)15.9 / 6.1 (48 V), 21.4 / 6.1 (72 V)23.8 / 6.5 (72 V), 25.6 / 6.5 (96 V)
Gross weight (kg) 9.8 / 5.1 (24 V), 12.1 / 5.1 (36 V)17.3 / 7.5 (48 V), 23.1 / 7.5 (72 V)25.6 / 8.0 (72 V), 27.3 / 8.0 (96 V)

Derate capacity to 90% when the output voltage is adjusted to 208 Vac. S = standard model, H = long time model (weights given as S / H). All specifications are subject to change without notice. Custom-made specifications are acceptable.

Downloads

Datasheets & manuals

Official Deltron documents for UPS 1-3 kVA – Deltron 101 Series. All files are PDF.

Contact us

Need a UPS sized for your project?

Need support or want to discuss your power protection needs? Our engineers will size the right UPS, stabilizer or transfer switch for your application.