Overview
UPS 20 – 200 kVA Modular – MTI200 Series
MTI200 series is modular online UPS for sensitive equipments. The single cabinet power rating covers from 20kVA to 200kVA which delivers the best of combination of reliability, hot-swappable and flexibility.
With the latest IGBT 3-level technology and DSP control, MTI200 achieves a high input power factor, low THDI.
Features
General Specifications
- Modular design with N+X redundancy
- Online hot swapping, by-pass and power module feature
- Full DSP control of high stability, reliability and safety
- 3 Level topology
- Excellent input performances for complete compatibility with input PF of 99% and wide range of voltage
- Self-Aging mode for full load test with less than 10% of the total power capacity needed
- Smart charging management system, intelligently control the whole process of the charging and discharging effectively improve the life time of the battery
- Independent charger for batteries, intelligent battery management system
- Battery cold start, UPS can be powered on from the battery without utility
- Totally front access, top and bottom cable connection
- User friendly machine interface with touch screen
- Hot swap battery system in single cabinet up to 60kVA
Technical specifications
UPS 20 – 200 kVA Modular – MTI200 Series – technical data
| Model | MTI2060/20 | MTI2120/20 | MTI2200/20 | MTI2060/20B * |
|---|---|---|---|---|
| Power (kVA) | 20 – 400 kVA | 20 – 400 kVA | 20 – 400 kVA | 20 – 60 kVA |
| Power module type | TPM 20 (20 kVA / 18 kW) | |||
| Input | ||||
| Phase | 3P + N + G | |||
| Voltage | 380 V / 400 V / 415 V (line to line) | |||
| Frequency | 50 Hz / 60 Hz | |||
| Power factor | > 0.99 | |||
| THDI | THDI < 3% @ 100% linear load | |||
| Voltage range | −20% – +25% | |||
| Frequency range | 40 Hz – 70 Hz | |||
| Output | ||||
| Voltage | 380 V / 400 V / 415 V | |||
| Voltage regulation | ±1% (balance load); ±1.5% (unbalance load) | |||
| Voltage THD | THD < 1.5% (linear load), THD < 6% (none linear load) | |||
| Power factor | 0.9 | |||
| Crest ratio | 3:1 | |||
| Overload capability | 110% for 1 hour; 125% for 10 minutes; 150% for 1 minute; > 150% for 200 ms | |||
| Battery | ||||
| Voltage | ±240 VDC for 40 batteries (selectable battery number 36 – 44) | |||
| Charge power | 20% × system power | |||
| Charge power precision | ±1% | |||
| System | ||||
| Parallel | 6 | 3 | 2 | – |
| System efficiency | Normal mode: 95%; ECO mode: 98%; battery mode: 95% | |||
| Display | LCD + LED, touch screen + keyboard | |||
| IP class | IP20 | |||
| Interface (communication port) | Standard: RS232, RS485, dry contacts, EPO / optional: SNMP card | |||
| Operation / storage temperature | 0 – 40 °C / −40 – 70 °C | |||
| Relative humidity | 0 – 95% (non-condensing) | |||
| Noise | 55 dB (1 meter away) | |||
| Physical | ||||
| Weight – cabinet (kg) | 3-slot cabinet: 120 | 6-slot cabinet: 151 | 10-slot cabinet: 182 | 3-slot cabinet: 205 |
| Weight – power module (kg) | TPM 20: 22 | |||
| Weight – battery pack (kg) | – | – | – | 10 (without battery) |
| Dimension – cabinet H × W × D (mm) | 3-slot cabinet: 1100 × 900 × 600 | 6-slot cabinet: 1600 × 900 × 600 | 10-slot cabinet: 2000 × 900 × 600 | 3-slot cabinet: 2000 × 600 × 1020 |
| Dimension – power module (mm) | TPM 20: (3U) 134 × 440 × 590 | |||
| Dimension – battery pack (mm) | – | – | – | (4U) 177 × 120 × 824 |
(*) Single cabinet with internal batteries.
Downloads
Datasheets & manuals
Official Deltron documents for UPS 20 – 200 kVA Modular – MTI200 Series. All files are PDF.
Related products
More UPS models
1-3kVA
Deltron 101 Series
High-Efficiency Power Protection
View details
6-10kVA
Deltron 106 Series
High-Efficiency Power Protection
View details
10-30kVA
DS Power H
The new DS Power range UPS uses the latest DSP technology to be programmed to suit a wide variety of electrical environments without impending its performance. With the DS Power range, efficiency, reliability and functionality are enhanced to levels unattainable with the old analogue technology. This technology does not only create significant increase in MTBF, but the capability of DSP to accurately manipulate signals at very high speed permits all the UPS subsystems to be controlled with greatly increased precision.
View details