Uninterruptible Power Supplies

UPS 100 – 300 kVA – DLT 3000 Series True Online UPS

Power range
100 – 300 kVA
Phase
Three phase (3/3)
Series
DLT 3000 Series
Category
Uninterruptible Power Supplies
Deltron DLT 3000 series 100-300 kVA UPS cabinet

Overview

UPS 100 – 300 kVA – DLT 3000 Series True Online UPS

100-300kva True online, Double conversion UPS Systems, manufactured with the state of the art, PWM and IGBT technology, producing microprocessor controlled pure sinewave output to critical loads.

Features

General Specifications

  • Output isolation transformer
  • Up to 92% efficiency
  • Static by-pass
  • LCD front panel
  • 128 events alarm memory (4000 alarms)
  • RS232 and relay contacts
  • Custom input and output voltage ranges
  • SNMP compatible communication
  • T-MON remote monitoring software
  • Parallel operation up to 4 devices
  • High performance at nonlinear loads
  • Custom input voltage and frequency ranges
  • Manufactured according to EC Directive; EN62040
  • 2 years warranty

Technical specifications

UPS 100 – 300 kVA – DLT 3000 Series True Online UPS – technical data

Technical specifications – DLT 3100 … DLT 3300
Model DLT 3100DLT 3120DLT 3160DLT 3200DLT 3250DLT 3300
Power 100 kVA120 kVA160 kVA200 kVA250 kVA300 kVA
Input
Voltage 220 / 400 Vac 3 phase + N, ±15%
By-pass voltage 220 / 400 Vac 3 phase + N, ±10%
Input frequency 50 Hz, ±5%
EMI EN50091-2 Class A
Input out of tolerance protection Electronic input out of tolerance protection
Output
Power (kW) 8096128160200240
Power factor 0.8
Voltage 220 / 400 Vac 3 phase + N
Frequency 50 Hz (60 Hz on request)
Frequency tolerance ±2% (line synchronized) / ±0.2% (free running)
Efficiency at 100% load 90 – 92%
Crest factor 3:1
Overload protection 100 – 125% load: 10 min, 125 – 150% load: 1 min, > 150% load: by-pass
Short circuit protection Electronic short circuit protection
Voltage out of tolerance protection Electronic out of tolerance protection
Total harmonic distortion < 3%
THD Non linear load < 5%
Batteries
Battery type Sealed lead acid – maintenance free
Number of batteries 303030303232
Float charging voltage 405 VDC405 VDC405 VDC405 VDC432 VDC432 VDC
End of discharge voltage 300 VDC300 VDC300 VDC300 VDC320 VDC320 VDC
Ambient temperature 25 °C
Battery voltage protection Electronic battery out of tolerance protection
Battery protection Automatic circuit breaker
Battery test Automatic every 72 hours
General
Communication RS232 + dry contacts
Temperature range 0 °C – 40 °C
Humidity (non condensed) 90% (non condensed)
Protection degree IP20
Altitude < 1000 m above sea level
Noise level < 65 dBA< 65 dBA< 65 dBA< 70 dBA< 70 dBA< 70 dBA
Weight without batteries (kg) 75076581097013301370
Dimensions H × W × D (mm) 1650 × 1100 × 8001650 × 1100 × 8001730 × 1195 × 8701730 × 1195 × 8701880 × 1565 × 9251880 × 1565 × 925
Ventilation Forced air cooling
Options
Input transformers Galvanic isolation transformer at the input (in the external cabinet)
Input THD < 10% (with 18 pulse rectifier, according to UPS range); 5% (with 18 pulse rectifier + filter) up to 80 kVA
Parallel operation 1+3 systems (N+1 redundant, redundant, symmetric parallel)
MBS Maintenance by-pass switch for complete isolation (for 206, 207 & 210)
Accessories
Monitoring and control software T-MON 3 client standard
Multiserver shutdown unit Available as option
SNMP communication adaptor Available as option
Serial port enhancer Available as option
ModBus communication adaptor Available as option (over RS485 or over TCP/IP)