Overview
UPS 100 – 300 kVA – DLT 3000 Series True Online UPS
100-300kva True online, Double conversion UPS Systems, manufactured with the state of the art, PWM and IGBT technology, producing microprocessor controlled pure sinewave output to critical loads.
Features
General Specifications
- Output isolation transformer
- Up to 92% efficiency
- Static by-pass
- LCD front panel
- 128 events alarm memory (4000 alarms)
- RS232 and relay contacts
- Custom input and output voltage ranges
- SNMP compatible communication
- T-MON remote monitoring software
- Parallel operation up to 4 devices
- High performance at nonlinear loads
- Custom input voltage and frequency ranges
- Manufactured according to EC Directive; EN62040
- 2 years warranty
Technical specifications
UPS 100 – 300 kVA – DLT 3000 Series True Online UPS – technical data
| Model | DLT 3100 | DLT 3120 | DLT 3160 | DLT 3200 | DLT 3250 | DLT 3300 |
|---|---|---|---|---|---|---|
| Power | 100 kVA | 120 kVA | 160 kVA | 200 kVA | 250 kVA | 300 kVA |
| Input | ||||||
| Voltage | 220 / 400 Vac 3 phase + N, ±15% | |||||
| By-pass voltage | 220 / 400 Vac 3 phase + N, ±10% | |||||
| Input frequency | 50 Hz, ±5% | |||||
| EMI | EN50091-2 Class A | |||||
| Input out of tolerance protection | Electronic input out of tolerance protection | |||||
| Output | ||||||
| Power (kW) | 80 | 96 | 128 | 160 | 200 | 240 |
| Power factor | 0.8 | |||||
| Voltage | 220 / 400 Vac 3 phase + N | |||||
| Frequency | 50 Hz (60 Hz on request) | |||||
| Frequency tolerance | ±2% (line synchronized) / ±0.2% (free running) | |||||
| Efficiency at 100% load | 90 – 92% | |||||
| Crest factor | 3:1 | |||||
| Overload protection | 100 – 125% load: 10 min, 125 – 150% load: 1 min, > 150% load: by-pass | |||||
| Short circuit protection | Electronic short circuit protection | |||||
| Voltage out of tolerance protection | Electronic out of tolerance protection | |||||
| Total harmonic distortion | < 3% | |||||
| THD | Non linear load < 5% | |||||
| Batteries | ||||||
| Battery type | Sealed lead acid – maintenance free | |||||
| Number of batteries | 30 | 30 | 30 | 30 | 32 | 32 |
| Float charging voltage | 405 VDC | 405 VDC | 405 VDC | 405 VDC | 432 VDC | 432 VDC |
| End of discharge voltage | 300 VDC | 300 VDC | 300 VDC | 300 VDC | 320 VDC | 320 VDC |
| Ambient temperature | 25 °C | |||||
| Battery voltage protection | Electronic battery out of tolerance protection | |||||
| Battery protection | Automatic circuit breaker | |||||
| Battery test | Automatic every 72 hours | |||||
| General | ||||||
| Communication | RS232 + dry contacts | |||||
| Temperature range | 0 °C – 40 °C | |||||
| Humidity (non condensed) | 90% (non condensed) | |||||
| Protection degree | IP20 | |||||
| Altitude | < 1000 m above sea level | |||||
| Noise level | < 65 dBA | < 65 dBA | < 65 dBA | < 70 dBA | < 70 dBA | < 70 dBA |
| Weight without batteries (kg) | 750 | 765 | 810 | 970 | 1330 | 1370 |
| Dimensions H × W × D (mm) | 1650 × 1100 × 800 | 1650 × 1100 × 800 | 1730 × 1195 × 870 | 1730 × 1195 × 870 | 1880 × 1565 × 925 | 1880 × 1565 × 925 |
| Ventilation | Forced air cooling | |||||
| Options | ||||||
| Input transformers | Galvanic isolation transformer at the input (in the external cabinet) | |||||
| Input THD | < 10% (with 18 pulse rectifier, according to UPS range); 5% (with 18 pulse rectifier + filter) up to 80 kVA | |||||
| Parallel operation | 1+3 systems (N+1 redundant, redundant, symmetric parallel) | |||||
| MBS | Maintenance by-pass switch for complete isolation (for 206, 207 & 210) | |||||
| Accessories | ||||||
| Monitoring and control software | T-MON 3 client standard | |||||
| Multiserver shutdown unit | Available as option | |||||
| SNMP communication adaptor | Available as option | |||||
| Serial port enhancer | Available as option | |||||
| ModBus communication adaptor | Available as option (over RS485 or over TCP/IP) | |||||
Downloads
Datasheets & manuals
Official Deltron documents for UPS 100 – 300 kVA – DLT 3000 Series True Online UPS. All files are PDF.
Related products
More UPS models
1-3kVA
Deltron 101 Series
High-Efficiency Power Protection
View details
6-10kVA
Deltron 106 Series
High-Efficiency Power Protection
View details
10-30kVA
DS Power H
The new DS Power range UPS uses the latest DSP technology to be programmed to suit a wide variety of electrical environments without impending its performance. With the DS Power range, efficiency, reliability and functionality are enhanced to levels unattainable with the old analogue technology. This technology does not only create significant increase in MTBF, but the capability of DSP to accurately manipulate signals at very high speed permits all the UPS subsystems to be controlled with greatly increased precision.
View details