Overview
UPS 10 – 800 kVA – Online UPS with Inverter Isolation Transformer
10-800kVA Online UPS are microprocessor controlled, full sine output uninterruptible power supplies produced with PWM (Pulse width modulation) and IGBT technologies. It provides uninterrupted energy for local networks, communication systems, sensitive medical devices, smart engineering measuring devices and industrial automation systems by guaranteeing safe operation thanks to its built-in inverter isolation transformer.
Features
General Specifications
- Operation Independent of Input Voltage and Frequency according to VFI-SS-111 Standard
- DSP Controlled IGBT Rectifier – IGBT Inverter – Battery Charging System
- Wide Input Voltage Range
- High Input Power Factor (>99%)
- Up to 94% High-Efficiency On-Line
- Up to 98% High-Efficiency in Eco-Mode
- True Full Sine Output Waveform, Low Harmonic Distortion
- Static and Manual By-Pass
- Electromagnetic and RFI Protection
- Digital Panel provides detailed information about Mains, Charging System, Battery Status, and Output Voltage
- Intelligent Charging System that ensures the long life of the batteries
- Communication via RS 232 Serial Port for remote monitoring and safe shutdown in networks, Smart Relay Contact Outputs
- Smart Fan; Speed Control for silent operation
- Custom made; according to needs, Input / Output values
Applications & Advantages
- IT Centers
- Factories
- Medical Devices
- Emergency Systems (Alarm)
- Communication Devices
- Server Rooms
- Industrial Applications
- Personal Computers
- Small Computer Network
- Network Systems
Advantages
- Latest Technology
- Energy save
- Clean and Constant Output Voltage
- Overload and Short Circuit Protection
- Remote Monitoring
- Adjustable Values
- Generator Compatibility
Technical specifications
UPS 10 – 800 kVA – Online UPS with Inverter Isolation Transformer – technical data
| Model | TRP-10 | TRP-20 | TRP-30 | TRP-40 | TRP-45 | TRP-60 | TRP-80 | TRP-100 | TRP-120 |
|---|---|---|---|---|---|---|---|---|---|
| Power | 10 kVA | 20 kVA | 30 kVA | 40 kVA | 45 kVA | 60 kVA | 80 kVA | 100 kVA | 120 kVA |
| Input | |||||||||
| Voltage | 380 / 400 / 415 VAC 3 phases + N | ||||||||
| Voltage tolerance | ±5% – 20% (adjustable) | ||||||||
| Power factor (full load) | ≥ 0.99 | ||||||||
| Frequency | 50/60 Hz ±5% | ||||||||
| THDi | < 4% | ||||||||
| Bypass | |||||||||
| Dual input connection | Standard | ||||||||
| Voltage | 380 / 400 / 415 VAC 3 phases + N | ||||||||
| Voltage tolerance | ±10% (adjustable) | ||||||||
| Frequency | 50/60 Hz | ||||||||
| Frequency tolerance | ±10% (adjustable) | ||||||||
| Output | |||||||||
| Voltage | 380 / 400 / 415 VAC 3 phases + N | ||||||||
| Voltage tolerance | ±1% (at static load), according to VFI-SS-111 at dynamic load | ||||||||
| Frequency | 50 Hz / 60 Hz (optional) | ||||||||
| Frequency tolerance | ±0.1% (without power grid), ±4% (synchron with power grid, adjustable ±5%) | ||||||||
| Power factor | 0.8 (optional 0.9 / 1) | ||||||||
| THDv | < 3% linear load, < 5% nonlinear load (IEC/EN 62040-3) | ||||||||
| Crest factor | 3:1 | ||||||||
| Overload capacity | |||||||||
| 100 – 110% | Normal mode continuously | ||||||||
| 110 – 125% | 10 min | ||||||||
| 125 – 150% | 1 min | ||||||||
| > 150% | Bypass mode | ||||||||
| Battery | |||||||||
| Number of batteries | 60 pieces (+405 VDC / −405 VDC) | ||||||||
| Battery protection | Deep discharge protection | ||||||||
| Battery test | Auto / manual | ||||||||
| Efficiency | |||||||||
| Online mode (full load) | > 92% | > 92% | > 92% | > 92% | > 92% | > 92% | > 93% | > 93% | > 93% |
| Eco-mode (full load) | > 98% | ||||||||
| General | |||||||||
| Topology | True online – double conversion, IGBT rectifier & inverter | ||||||||
| Control technology | 3 pieces DSP processor, SPWM | ||||||||
| Indicators | Graphic LCD panel, mimic diagram, control keys, warning LED error indicators | ||||||||
| Options | |||||||||
| Parallel operation | Up to 6 units | ||||||||
| Communication | SNMP, RS232, RS485, MODBUS | ||||||||
| Remote monitoring | SNMP view, UPSMon, remote panel | ||||||||
| Dry contact relay outputs | Programmable 5 dry contacts | ||||||||
| Custom inputs | Generator, battery temperature control, remote emergency power off (EPO) | ||||||||
| Operation conditions | |||||||||
| Operating temperature | 0 °C – 40 °C | ||||||||
| Humidity | 0% – 95% (non-condensing) | ||||||||
| Altitude | ≤ 2000 m | ||||||||
| Noise level (1 meter) | < 55 dB(A) | < 55 dB(A) | < 55 dB(A) | < 60 dB(A) | < 60 dB(A) | < 60 dB(A) | < 60 dB(A) | < 65 dB(A) | < 65 dB(A) |
| Physical conditions | |||||||||
| Battery cabinet | Internal | Internal | Internal | Internal | External | External | External | External | External |
| Dimensions W × D × H (mm) | 350 × 795 × 1110 | 350 × 795 × 1110 | 350 × 795 × 1110 | 500 × 806 × 1213 | 500 × 806 × 1213 | 500 × 806 × 1213 | 500 × 806 × 1213 | 550 × 800 × 1335 | 550 × 800 × 1335 |
| Weight (kg, without battery) | 82 | 85 | 90 | 100 | 110 | 165 | 172 | 290 | 315 |
| Protection class | IP 20 | ||||||||
| Model | TRP-160 | TRP-200 | TRP-250 | TRP-300 | TRP-400 | TRP-500 | TRP-600 | TRP-800 |
|---|---|---|---|---|---|---|---|---|
| Power (kVA) | 160 | 200 | 250 | 300 | 400 | 500 | 600 | 800 |
| Input | ||||||||
| Voltage | 380 / 400 / 415 VAC 3 phases + N | |||||||
| Voltage tolerance | ±5% – 20% (adjustable) | |||||||
| Power factor (full load) | ≥ 0.99 | |||||||
| Frequency | 50/60 Hz ±10% | |||||||
| THDi | < 4% | |||||||
| Bypass | ||||||||
| Dual input connection | Standard | |||||||
| Voltage | 380 / 400 / 415 VAC 3 phases + N | |||||||
| Voltage tolerance | ±10% (adjustable) | |||||||
| Frequency | 50/60 Hz | |||||||
| Frequency tolerance | ±10% (adjustable) | |||||||
| Output | ||||||||
| Voltage | 380 / 400 / 415 VAC 3 phases + N | |||||||
| Voltage tolerance | ±1% (at static load), according to VFI-SS-111 at dynamic load | |||||||
| Frequency | 50 Hz / 60 Hz (optional) | |||||||
| Frequency tolerance | ±0.1% (without power grid), ±4% (synchron with power grid, adjustable ±5%) | |||||||
| Power factor | 0.8 (optional 0.9 / 1) | |||||||
| THDv | < 3% linear load, < 5% nonlinear load (IEC/EN 62040-3) | |||||||
| Crest factor | 3:1 | |||||||
| Overload capacity | ||||||||
| 100 – 110% | Normal mode continuously | |||||||
| 110 – 125% | 10 min | |||||||
| 125 – 150% | 1 min | |||||||
| > 150% | Bypass mode | |||||||
| Battery | ||||||||
| Number of batteries | 60 pieces (+405 VDC / −405 VDC) | |||||||
| Battery protection | Deep discharge protection | |||||||
| Battery test | Auto / manual | |||||||
| Efficiency | ||||||||
| Online mode (full load) | > 93% | > 94% | > 94% | > 94% | > 94% | > 94% | > 94% | > 94% |
| Eco-mode (full load) | > 98% | |||||||
| General | ||||||||
| Topology | True online – double conversion, IGBT rectifier & inverter | |||||||
| Control technology | 3 pieces DSP processor, SPWM | |||||||
| Indicators | Graphic LCD panel, mimic diagram, control keys, warning LED error indicators | |||||||
| Options | ||||||||
| Parallel operation | Up to 6 units | |||||||
| Communication | SNMP, RS232, RS485, MODBUS | |||||||
| Remote monitoring | SNMP view, UPSMon, remote panel | |||||||
| Dry contact relay outputs | Programmable 5 dry contacts | |||||||
| Custom inputs | Generator, battery temperature control, remote emergency power off (EPO) | |||||||
| Operation conditions | ||||||||
| Operating temperature | 0 °C – 40 °C | |||||||
| Humidity | 0% – 95% (non-condensing) | |||||||
| Altitude | ≤ 2000 m | |||||||
| Noise level (1 meter) | < 70 dB(A) | < 70 dB(A) | < 75 dB(A) | < 75 dB(A) | < 75 dB(A) | < 75 dB(A) | < 75 dB(A) | < 75 dB(A) |
| Physical conditions | ||||||||
| Battery cabinet | External | |||||||
| Dimensions W × D × H (mm) | 685 × 1007 × 1755 | 685 × 1007 × 1755 | 685 × 1007 × 1755 | 1600 × 868 × 1800 | 1600 × 868 × 1800 | 1600 × 868 × 1800 | 3216 × 868 × 1800 | 3216 × 868 × 1800 |
| Weight (kg, without battery) | 400 | 500 | 600 | 850 | 950 | 1200 | 1400 | 2100 |
| Protection class | IP 20 | |||||||
Downloads
Datasheets & manuals
Official Deltron documents for UPS 10 – 800 kVA – Online UPS with Inverter Isolation Transformer. All files are PDF.
Documents
Related products
More UPS models
1-3kVA
Deltron 101 Series
High-Efficiency Power Protection
View details
6-10kVA
Deltron 106 Series
High-Efficiency Power Protection
View details
10-30kVA
DS Power H
The new DS Power range UPS uses the latest DSP technology to be programmed to suit a wide variety of electrical environments without impending its performance. With the DS Power range, efficiency, reliability and functionality are enhanced to levels unattainable with the old analogue technology. This technology does not only create significant increase in MTBF, but the capability of DSP to accurately manipulate signals at very high speed permits all the UPS subsystems to be controlled with greatly increased precision.
View details