UPS 10 – 600 kVA – DS Power 300HT with Inverter Isolation Transformer
DS Power 300HT Online UPS uses the latest DSP technology, which can be programmed to suit a wide variety of electrical environments without impending its performance. With the 3-Level topology, efficiency, reliability and functionality have been raised to levels unattainable with old analog technology. This technology not only creates a significant increase in MTBF, but the DSP’s ability to accurately process signals at very high speed allows all UPS subsystems to be controlled with greatly increased precision. Thanks to its built-in inverter isolation transformer, it guarantees safe operation and provides uninterrupted energy for local networks, communication systems, sensitive medical devices, smart engineering measurement devices and industrial automation systems.
Features
General Specifications
- Inverter isolation transformer
- 3 DSP controlled modular structure
- Separate main control board advantage for rectifier and inverter
- 3-Level technology and fully digital structure
- Less electronic components and SMD technology
- Low input current total harmonic distortion (THD)
- High input power factor
- High efficiency up to 94%
- Selectable input/output voltage/frequency range
- Static and maintenance by-pass switch
- High charge current capacity
- Eco Mode operation (optional)
- Split by-pass input (dual input)
- Advanced TFT front panel (40-500kVA)
- Cold start function
- Compliant with IEC EN62040 directive
- Conforms to CE, TSE and GOST standards
- ISO9001, ISO14001 compliant production
- Advanced control at the input
- 3 level battery protection
- Temperature compensated charge system
- Output current limitation
- Output DC leakage protection
- Output short circuit and overload protection
- External REPO input
- 512 events memory (46.000 alarm)
- Clock and calendar (battery supported)
- Automatic battery test, remaining battery time indicator
- 2 RS232 serial ports and 4 programmable dry contact outputs
- Optional 12 dry contact outputs
- Optional SNMP, MODBUS and Remote Monitoring Panel
- Viewing device operating parameters
- Advanced remote control features
- User and central service password-protected security
- 2 years warranty
Technical specifications
UPS 10 – 600 kVA – DS Power 300HT with Inverter Isolation Transformer – technical data
| Model | DS310T | DS315T | DS320T | DS330T | DS340T | DS360T | DS380T | DS3100T | DS3120T | DS3160T | DS3200T | DS3250T | DS3300T | DS3400T | DS3500T | DS3600T |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Power (kVA) | 10 | 15 | 20 | 30 | 40 | 60 | 80 | 100 | 120 | 160 | 200 | 250 | 300 | 400 | 500 | 600 |
| Input | ||||||||||||||||
| Voltage | 380/400 VAC 3P + N + G ±20% (415 VAC +15%, −25% optional) | |||||||||||||||
| Frequency | 50 Hz / 60 Hz, ±5% | |||||||||||||||
| Power factor | > 0.99 | |||||||||||||||
| THDI (*) | 3% | |||||||||||||||
| By-pass voltage | 380/400 VAC 3 phase + N, 4 wires, ±10% | |||||||||||||||
| Voltage distortion | < 10% | |||||||||||||||
| Protection | Fuses, voltage & frequency tolerance, input power limit, phase sequence indicator | |||||||||||||||
| Output | ||||||||||||||||
| Power (kW) | 9 | 13.5 | 18 | 27 | 36 | 54 | 72 | 90 | 108 | 144 | 180 | 225 | 270 | 360 | 450 | 540 |
| Power factor | 0.9 | |||||||||||||||
| Voltage | 380/400 VAC 3P + N, ±1% (415 VAC optional) | |||||||||||||||
| Frequency | 50 Hz / 60 Hz | |||||||||||||||
| Frequency tolerance | Line synchronized: ±2% / free running: ±0.1% | |||||||||||||||
| Efficiency | up to 93% | |||||||||||||||
| Crest factor | 3:1 | |||||||||||||||
| Overload protection | 100 – 125% load: 10 min, 125 – 150% load: 1 min, > 150% load: by-pass | |||||||||||||||
| Other protections | Advanced short circuit, voltage tolerance, DC balance, regenerative load, current limiting | |||||||||||||||
| Voltage THD | < 3% (at 100% linear load) | |||||||||||||||
| Batteries | ||||||||||||||||
| Type | VRLA AGM / GEL / NiCd | |||||||||||||||
| Nominal voltage | ±312 VDC (2 × 26 batteries) | |||||||||||||||
| Float / end of discharge voltage | ±351 VDC / ±260 VDC | |||||||||||||||
| Battery cabinet | External | |||||||||||||||
| Battery ambient temperature | 25 °C | |||||||||||||||
| Protections | 3 level alarms, battery fuses, charging current limit, temperature compensation (optional) | |||||||||||||||
| Automatic testing | Standard every 72 hours (adjustable) | |||||||||||||||
| General | ||||||||||||||||
| Standards | EN62040-1, EN62040-2, EN62040-3 | |||||||||||||||
| User interface | 4 lines LCD panel, mimic LEDs, 5 vector buttons, buzzer, optional TFT panel | |||||||||||||||
| Indicators | P-N voltage, P-P voltage, current, power, crest factor, frequency, PF, service time | |||||||||||||||
| Advanced | Self diagnostics, 3 maintenance time indicators, calibration over RS232, operating hour meter | |||||||||||||||
| Communication | 2 × RS232 serial ports, 4 standard and 8 optional dry contact alarm relays | |||||||||||||||
| Inputs | EPO input, interactive battery panel input, genset input | |||||||||||||||
| Genset kit | Standard (programmable) | |||||||||||||||
| Software | Standard T-Mon UPS Management Software (3 clients + 1 server management) | |||||||||||||||
| Alarm logging | Standard: with time & date 512 events | |||||||||||||||
| Protections | Power module over-temperature, over current, temperature high alarm | |||||||||||||||
| Temperature range | 0 °C – 40 °C | |||||||||||||||
| Protection degree | IP20 | |||||||||||||||
| Relative humidity | 90% max. (non-condensing) | |||||||||||||||
| Altitude | < 1000 m above sea level | |||||||||||||||
| Acoustic noise | < 57 dBA | < 57 dBA | < 62 dBA | < 62 dBA | < 62 dBA | < 64 dBA | < 64 dBA | < 64 dBA | < 68 dBA | < 68 dBA | < 68 dBA | < 72 dBA | < 72 dBA | < 72 dBA | < 72 dBA | < 72 dBA |
| Weight (kg) | 187 | 198.5 | 244 | 270 | 393 | 457 | 536 | 539 | 595 | 647 | 910.5 | 1150 | 1283 | 1497 | 1702 | 1875 |
| Dimensions H × W × D (mm) | 1040 × 400 × 815 | 1040 × 400 × 815 | 1040 × 400 × 815 | 1040 × 400 × 815 | 1440 × 515 × 855 | 1440 × 515 × 855 | 1440 × 515 × 855 | 1770 × 825 × 855 | 1770 × 825 × 855 | 1770 × 825 × 855 | 1770 × 825 × 855 | 1900 × 1250 × 1055 | 1900 × 1250 × 1055 | 1900 × 1250 × 1055 | 1900 × 1250 × 1055 | 1900 × 1250 × 1055 |
| Options | ||||||||||||||||
| Different input / output voltage | Please ask | |||||||||||||||
| Software | T-Mon Admin multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients | |||||||||||||||
| Adaptors | SNMP, RS485, remote monitoring panel, MODBUS (RS485 or TCP/IP), USB alarm logger, TCP/IP, GSM/GPRS modem, com port multiplexer | |||||||||||||||
| Parallel operation | up to 8 | |||||||||||||||
(*) Depending on power and input/output conditions.
Downloads
Datasheets & manuals
Official Deltron documents for UPS 10 – 600 kVA – DS Power 300HT with Inverter Isolation Transformer. All files are PDF.
Related products
More UPS models
1-3kVA
Deltron 101 Series
High-Efficiency Power Protection
View details
6-10kVA
Deltron 106 Series
High-Efficiency Power Protection
View details
10-30kVA
DS Power H
The new DS Power range UPS uses the latest DSP technology to be programmed to suit a wide variety of electrical environments without impending its performance. With the DS Power range, efficiency, reliability and functionality are enhanced to levels unattainable with the old analogue technology. This technology does not only create significant increase in MTBF, but the capability of DSP to accurately manipulate signals at very high speed permits all the UPS subsystems to be controlled with greatly increased precision.
View details