Uninterruptible Power Supplies

UPS 10 – 160 kVA – Three-Phase IGBT Transformerless UPS

Power range
10 – 160 kVA
Phase
Three phase (3/3)
Category
Uninterruptible Power Supplies
Deltron 10-160 kVA three-phase online UPS

Overview

UPS 10 – 160 kVA – Three-Phase IGBT Transformerless UPS

Cold Start · High Input Power Factor · High efficiency up to 94% · External REPO switch input · IGBT Transformerless Technology · DSP Control.

Features

General Specifications

  • Low input current total harmonic distortion (THD)
  • Static and maintenance bypass switch
  • Output and by-pass short circuit and overload protection
  • 192 events memory (192 events 4500 alarms)
  • Clock and calendar (battery supported)
  • Automatic battery test, remaining battery time indicator
  • Temperature compensated charge system
  • Regenerative backfeed function
  • 2 RS232 serial port and 12 dry contact outputs
  • 3 DSP controlled modular structure
  • Optional graphical and touch panel
  • CE, ISO9001, ISO14001 certification
  • 2 years warranty
  • 10 years spare parts support

Technical specifications

UPS 10 – 160 kVA – Three-Phase IGBT Transformerless UPS – technical data

Technical specifications – 10 – 160 kVA three-phase UPS (DS Power range)
Model 10152030406080100120160200250300400
Power (kVA) 10152030406080100120160200250300400
Input
Voltage 380/400 VAC 3P + N + G ±20% (at 100% load) / −40% (at 70% load)
Frequency 50 Hz / 60 Hz, ±5%
Power factor (at 100% load) ≥ 0.99
THDI (*) ≤ 3%
By-pass voltage 380/400 VAC 3 phase + N, ±10%
Voltage distortion ≤ 10%
Protections Fuses, voltage & frequency tolerance, input power limit, phase sequence indicator
Output
Power (kW) 913.5182736547290108144180225270360
Power factor 0.9 (0.8 and 1 optional)
Voltage 380/400 VAC 3P + N, ±1% (415 VAC optional)
Frequency 50 Hz / 60 Hz
Frequency tolerance Line synchronized: ±2% (adjustable) / free running: ±0.1%
Efficiency up to 95%
Crest factor 3:1
Overload capacity 100 – 125% load: 10 min, 125 – 150% load: 1 min, > 150% load: by-pass
Other protections Advanced short circuit, voltage tolerance, DC balance, regenerative load, current limiting
Voltage THD ≤ 3% (at 100% linear load)
Battery
Type VRLA AGM / GEL / NiCd
Number of batteries 2 × 30 (±30): 60 pieces
Charge voltage 2 × 405 VDC
End of discharge voltage 2 × 300 VDC
Battery cabinet Internal (10 – 80 kVA) / External (100 – 400 kVA)
Battery ambient temperature 25 °C
Protections 3 level alarms, battery fuses, charging current limit, temperature compensation (optional)
Automatic testing Standard every 72 hours (adjustable)
General
Standards EN62040-1, EN62040-2, EN62040-3
User interface 4 lines LCD panel, mimic LEDs, 5 vector buttons, buzzer, optional TFT panel
Indicators P-N voltage, P-P voltage, current, power, crest factor, frequency, PF, service time
Advanced Self diagnostics, 3 maintenance time indicators, calibration over RS232, operating hour meter
Communication 2 × RS232 serial ports, 4 standard and 8 optional dry contact alarm relays
Inputs EPO input, interactive battery panel input, genset input
Genset kit Standard (programmable)
Software Standard T-Mon UPS Management Software (3 clients + 1 server management)
Alarm logging Standard: with time & date 512 events
Protections Power module over-temperature, overcurrent, temperature high alarm
Temperature ranges 0 °C – 40 °C
Protection degree IP20
Relative humidity 95% max. (non-condensing)
Altitude < 1000 m above sea level
Acoustic noise < 57 dBA< 57 dBA< 57 dBA< 57 dBA< 62 dBA< 62 dBA< 62 dBA< 65 dBA< 65 dBA< 65 dBA< 68 dBA< 68 dBA< 68 dBA< 68 dBA
Net weight (kg) 878791100173197209220232265470525635680
Dimensions H × W × D (mm) 1040 × 400 × 8151040 × 400 × 8151040 × 400 × 8151040 × 400 × 8151440 × 515 × 8551440 × 515 × 8551440 × 515 × 8551440 × 515 × 8551440 × 515 × 8551440 × 515 × 8551900 × 880 × 7751900 × 880 × 7751900 × 1250 × 7751900 × 1250 × 775
Options
Different input / output voltage Please ask
Transformer Galvanic isolation transformer at the input & output (internal)
Software T-Mon Admin multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients
Adaptors SNMP, RS485, remote monitoring panel, MODBUS (RS485 or TCP/IP), USB alarm logger, TCP/IP, GSM/GPRS modem, com port multiplexer
Parallel operation up to 8 units

(*) Depending on power and input/output conditions.

Downloads

Datasheets & manuals

Official Deltron documents for UPS 10 – 160 kVA – Three-Phase IGBT Transformerless UPS. All files are PDF.

Contact us

Need a UPS sized for your project?

Need support or want to discuss your power protection needs? Our engineers will size the right UPS, stabilizer or transfer switch for your application.